RECTIFIER
1 Wide input voltage window - UPS operates and charges battery even when the incoming supply goes to as low as -30% and as high as +15% over the nominal (300V to 480V). The advantage to the user is that the Battery remains in top charged condition most of the time (even at low input supply voltage condition and which is very common in India) and provides full backup power only when the total power fails or the input supply is too low. This avoids unnecessary discharge of Battery bank. And this has a direct impact on battery life. The battery life expectancy is increased to a greater extent.
2 Input Power factor & current harmonic control - The rectifier is state of the art PWM IGBT Rectifier, with built in active input power factor and input current harmonic level control. These features differentiate against conventional controlled rectifier designs. The design offers Input Power Factor better than 0.99 and the current harmonic distrotion level less than 3% (in full load condition). Also, the input power factor and the current harmoic distortion levels are maintained well within the limits irrespective of load variation and input supply variation. In conventional rectifiers these two parameters varies with input supply change and also the percentage of load put on the system.
3 Reduction in generator sizing - The generator sizing required for ESTEEM UPS is considerably low (10% - more than the corresponding UPS input power). For conventional UPS's the generator sizing required is 40 to 60% more, hence more expenditure and more stress on your alternate source (i.e. generator), for which the user has maximum restriction on power usage.